top of page

Range

Acti9

Product name

Disbo iC60

product or component type

Miniature circuit-breaker

Device short name

IC60N

poles description

2P

Number of protected poles

2

[In] rated current

40 A

Network type

AC/DC

Trip unit technology

Thermal-magnetic

Curve code

C

Breaking capacity

10 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2 6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1 36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2

Utilisation category

Category A conforming to EN/IEC 60947-2

Complementary

Network frequency

50/60 Hz

[Ue] rated operational voltage

400 V AC 50/60 Hz

Magnetic tripping limit

8 x In +/- 20 %

[Ics] rated service breaking capacity

27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 6000 A 100 % conforming to EN/IEC 60898-1 - 415 V AC 50/60 Hz 6 kA 100 % conforming to EN/IEC 60947-2 - 100...133 V DC

Limitation class

3 conforming to EN/IEC 60947-2

[Ui] rated insulation voltage

500 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage

6 kV conforming to EN/IEC 60947-2

Contact position indicator

Yes

Control type

Toggle

local signalling

Trip indicator

mounting mode

Clip-on

mounting support

Rail

9 mm pitches

4

Height

85 mm

Width

36 mm

Depth

78.5 mm

net weight

0.25 kg

Colour

White

Mechanical durability

20000 cycles

Electrical durability

10000 cycles

Provision for padlocking

Padlockable

Connections - terminals

Single terminal (top or bottom) 1…35 mm² rigid Single terminal (top or bottom) 1…25 mm² flexible

Wire stripping length

14 mm for top or bottom connection

Tightening torque

3.5 N.m top or bottom

Earth-leakage protection

Separate block

Environment

Standards

EN/IEC 60898-1 EN/IEC 60947-2

IP degree of protection

IP20 conforming to IEC 60529

Pollution degree

3 conforming to EN/IEC 60947-2

Tropicalisation

2 conforming to IEC 60068-1

Relative humidity

95 % at 55 °C

Ambient air temperature for operation

-35…70 °C

ambient air temperature for storage

-40…85 °C

Packing Units

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

3.700 cm

Package 1 Width

7.300 cm

Package 1 Length

8.900 cm

Schneider Electric Acti9 iC60N, 2P, 40A, C curve, 6000A (IEC/EN 60898-1), 10k...

‏42.00 د.إ.‏Price
Quantity
No Reviews YetShare your thoughts. Be the first to leave a review.