Range

Multi9

Product name

Multi9 C60H-DC

product or component type

Miniature circuit-breaker

Device short name

C60H-DC

Device application

Distribution

poles description

2P

Number of protected poles

2

[In] rated current

40 A at 25 °C

Network type

DC

Trip unit technology

Thermal-magnetic

Curve code

C

Breaking capacity

20 kA Icu at 220 V DC conforming to GB 14048.2 10 kA Icu at 440 V DC conforming to GB 14048.2 6 kA Icu at 500 V DC conforming to GB 14048.2 20 kA Icu at 220 V DC conforming to EN/IEC 60947-2 10 kA Icu at 440 V DC conforming to EN/IEC 60947-2 6 kA Icu at 500 V DC conforming to EN/IEC 60947-2 5 kA AIR at 12...500 V DC conforming to UL 1077

Utilisation category

Category A conforming to EN/IEC 60947-2

Suitability for isolation

Yes conforming to EN/IEC 60947-2

Complementary

[Ue] rated operational voltage

12...500 V DC

Magnetic tripping limit

8.5 x In +/- 20 % AC

[Ics] rated service breaking capacity

4.5 kA 75 % conforming to GB 14048.2 - 500 V DC 7.5 kA 75 % conforming to GB 14048.2 - 440 V DC 15 kA 75 % conforming to GB 14048.2 - 220 V DC 15 kA 75 % conforming to EN/IEC 60947-2 - 220 V DC 7.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V DC 4.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V DC

Limitation class

3 conforming to EN/IEC 60947-2

[Ui] rated insulation voltage

500 V DC conforming to EN/IEC 60947-2

[Uimp] rated impulse withstand voltage

6 kV conforming to EN/IEC 60947-2

Contact position indicator

Yes

Control type

Toggle

local signalling

ON/OFF indication

mounting mode

Clip-on

mounting support

DIN rail

Comb busbar and distribution block compatibility

Top or bottom: standard

9 mm pitches

4

Height

81 mm

Width

36 mm

Depth

73 mm

net weight

0.256 kg

Colour

Grey

Mechanical durability

20000 cycles

Electrical durability

3000 cycles L/R = 2 ms

Provision for padlocking

Padlockable

Locking options description

In position O

Connections - terminals

Tunnel type terminal (top or bottom)1…35 mm² (AWG 18...AWG 2) - rigid stranded Tunnel type terminal (top or bottom)1…25 mm² (AWG 18...AWG 4) - flexible Tunnel type terminal (top or bottom)1…25 mm² (AWG 18...AWG 4) - flexible with ferrule Tunnel type terminal (top or bottom) - 2 cable(s) 1…16 mm² (AWG 18...AWG 6) - rigid stranded Tunnel type terminal (top or bottom) - 2 cable(s) 1…16 mm² (AWG 18...AWG 6) - flexible Tunnel type terminal (top or bottom) - 2 cable(s) 1…16 mm² (AWG 18...AWG 6) - flexible with ferrule Tunnel type terminal (top or bottom) - 3 cable(s) 4 mm² (AWG 6) - flexible stranded

Wire stripping length

14 mm for top or bottom connection

Tightening torque

3.5 N.m top or bottom

Earth-leakage protection

Without

Environment

Standards

UL 1077 GB 14048.2 EN/IEC 60947-2

Product certifications

UR CCC IEC

IP degree of protection

IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529

Pollution degree

3 conforming to EN/IEC 60947-2

Overvoltage category

IV

Tropicalisation

2 conforming to IEC 60068-2 2 conforming to GB 14048.2

Relative humidity

95 % at 55 °C

Operating altitude

2000 m

Ambient air temperature for operation

-25…70 °C

ambient air temperature for storage

-40…85 °C

Packing Units

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

7.1 cm

Package 1 Width

3.6 cm

Package 1 Length

8.5 cm

 